SISTEMA OPUESTO ACAJUTLA

###################################

 The working case has a largest mismatch of 0.0 MW at bus 6124 [MIR44       43.800]

 These subsystems were specified:
   # <------- SUBSYSTEM LABEL ------>  BUSES    # <------- SUBSYSTEM LABEL ------>  BUSES    # <------- SUBSYSTEM LABEL ------>  BUSES
   1 GUATEMALA                           575    2 ESAG1                                31    3 ESAG2                                23
   4 ELSALVADOR                           27    5 ESA                                  75    6 ELSALVADORM                          73
   7 ACAJUTLA                              8    8 HONDURAS                            334    9 GUA-HON                             909

 Study system generation is         625.1 MW
 Opposing system generation is      194.0 MW
 Study system net interchange is    624.8 MW
     PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS(R)E     THU, FEB 01 2018  16:39
 SISTEMA ELCTRICO REGIONAL - DEMANDA MAX NOC-2DO SEM18                   PAGE 1
 ESTUDIOS ERT 2018-2019
 ** TLTG IMPORT LIMIT OUTPUT FOR BASE CASE                                    **

 DISTRIBUTION FACTOR FILE:     G:\control\Estudios\ERT2018\Simulaciones\TLTG\2018-2019\ERT_MaxNoc2Sem18\Dfx_ERT_MaxNoc2Sem18.dfx
 SUBSYSTEM DESCRIPTION FILE:   G:\control\Estudios\ERT2018\Simulaciones\TLTG\2018-2019\subsistemas_TLTG.sub
 MONITORED ELEMENT FILE:       G:\control\Estudios\ERT2018\Simulaciones\TLTG\2018-2019\monitoreo_TLTG.mon
 CONTINGENCY DESCRIPTION FILE: G:\control\Estudios\ERT2018\Simulaciones\TLTG\2018-2019\ESA_TLTG_Cont.con

                                 PRE-SHIFT    DELTA  POST-SHIFT
 STUDY SYSTEM MW GENERATION:        625.1     -20.0     605.1
 OPPOSING SYSTEM MW GENERATION:     194.0      20.0     214.0
 STUDY SYSTEM NET INTERCHANGE:      624.8     -20.0     604.8

 <---------------- STUDY SYSTEM -----------------> <--------------- OPPOSING SYSTEM --------------->
                          <---- GENERATOR MW ---->                          <---- GENERATOR MW ---->
   BUS# X-- NAME --X BASKV    BASE   SHIFT  CHANGE   BUS# X-- NAME --X BASKV    BASE   SHIFT  CHANGE
  20301 SOYA-G1     4.1600    14.8    14.3    -0.5  21136 M1-M3       13.800    39.8    44.1     4.3
  21101 5NOV-U1     13.800    16.9    16.3    -0.6  21137 M4-M6       13.800    39.3    43.6     4.3
  21102 5NOV-U2     13.800    16.9    16.3    -0.6  21138 M7-M9       13.800    48.3    52.7     4.4
  21103 5NOV-U3     13.800    16.9    16.3    -0.6  21139 TPTO-G1     13.800    66.6    73.6     7.0
  21104 5NOV-U4     13.800    15.1    14.5    -0.5
  21106 5NOV-U6     13.800    35.6    34.4    -1.2
  21107 5NOV-U7     13.800    35.6    34.4    -1.2
  21111 GUAJ-U1     13.800    16.7    16.2    -0.6
  21171 CGRA-U1     13.800    83.8    81.3    -2.5
  21172 CGRA-U2     13.800    83.8    81.3    -2.5
  21181 15SE-U1     13.800    90.0    87.4    -2.6
  21182 15SE-U2     13.800    90.0    87.4    -2.6
  21304 TEXT-G1     13.800     6.6     6.4    -0.2
  21451 TEXT-G2     13.800    10.0     9.5    -0.5
  21481 TALN-G1     13.800    46.0    44.4    -1.7
  21482 TALN-G2     13.800    46.3    44.6    -1.7




























































































































































































































































































 LOADINGS AT OR ABOVE 100.0 <------------- BASE CASE ------------->
 OF RATING ARE MARKED WITH '*'                             INCR.          PRE-   POST-   LIMIT
                                                           TRANS RATING  SHIFT   SHIFT    CASE    DISTR.
 <------- F R O M -------> <--------- T O ---------> CKT   CAPAB    A      MW      MW      MW     FACTOR
  27131 ACAJ-115    115.00  27411 SONS-115    115.00  1   -261.4   130    50.4    56.5   130.0* -0.30448
  27161 AHUA-115    115.00  27411 SONS-115    115.00  1   -454.2   128   -13.6   -18.6   -79.2   0.25093
  27132 ACAJ2-115   115.00  27441 ATEO-115    115.00  1   -490.3   260    68.2    76.0   170.4  -0.39104
  27381 OPIC-115    115.00  27411 SONS-115    115.00  1   -538.3   130   -29.7   -33.4   -78.3   0.18592
  27411 SONS-115    115.00  27441 ATEO-115    115.00  1   -565.4   130    32.6    36.0    77.6  -0.17210
  27441 ATEO-115    115.00  27481 TALN-115    115.00  1   -747.7   260   -50.5   -42.2    57.9  -0.41465
  27361 SANT-115    115.00  27481 TALN-115    115.00  1   -911.2   260   -35.4   -40.3   -99.7   0.24596
  28161 AHUA-230    230.00 3WNDTR INTER 2      WND 1  2  -1229.8   149   -13.4   -15.6   -42.1   0.10994
  28161 AHUA-230    230.00 3WNDTR INTER 1      WND 1  1  -1294.9   156   -13.4   -15.6   -42.1   0.10994
  27381 OPIC-115    115.00  27501 SMAT-115    115.00  1  -1354.9   260     4.8     8.6    54.0  -0.18832
  27371 NEJA-115    115.00  27501 SMAT-115    115.00  1  -1430.8   260     9.5     5.7   -39.8   0.18832
  28181 15SE-230    230.00 3WNDTR INTER 4      WND 1  2  -1867.4   153   -29.0   -27.1    -3.5  -0.09759
  28181 15SE-230    230.00 3WNDTR INTER 3      WND 1  1  -1867.4   153   -29.0   -27.1    -3.5  -0.09759
  27371 NEJA-115    115.00  27171 CGRA-115    115.00  2  -2095.1   260   -80.3   -77.1   -37.9  -0.16242
  27371 NEJA-115    115.00  27171 CGRA-115    115.00  1  -2095.1   260   -80.3   -77.1   -37.9  -0.16242
  27321 SRAF-115    115.00  27431 SMAR-115    115.00  1  -2255.3   260    76.8    73.8    37.8   0.14931
  27101 5NOV-115    115.00  27321 SRAF-115    115.00  1  -2896.6   260    86.5    84.1    55.3   0.11953
  27161 AHUA-115    115.00  27351 SANA-115    115.00  1  -3201.1   128    28.7    29.3    36.8  -0.03105
  28161 AHUA-230    230.00  28371 NEJA-230    230.00  2  -4184.0   396     1.4     3.3    26.1  -0.09430
  28161 AHUA-230    230.00  28371 NEJA-230    230.00  1  -4184.0   396     1.4     3.3    26.1  -0.09430
  27181 15SE-115    115.00  27431 SMAR-115    115.00  1  -4713.3   130    35.4    34.7    26.2   0.03500
  27181 15SE-115    115.00  27431 SMAR-115    115.00  2  -4713.3   130    35.4    34.7    26.2   0.03500
  27171 CGRA-115    115.00  27321 SRAF-115    115.00  1  -4835.7   130    36.8    36.1    27.8   0.03449
  28181 15SE-230    230.00  28371 NEJA-230    230.00  2  -5319.4   396    40.3    38.6    18.9   0.08195
  28181 15SE-230    230.00  28371 NEJA-230    230.00  1  -5319.4   396    40.3    38.6    18.9   0.08195
  28371 NEJA-230    230.00 3WNDTR NEJA_TR_1    WND 1  1  -9038.1   153    41.7    42.0    44.9  -0.01235
  28371 NEJA-230    230.00 3WNDTR NEJA_TR_2    WND 1  2  -9038.2   153    41.7    42.0    44.9  -0.01235
  28181 15SE-230    230.00  29181 F-15SE-NNC  230.00  1  -26137.   521   -28.6   -28.9   -33.5   0.01883
  28161 AHUA-230    230.00  29162 F-AHU-MOY   230.00  1  -28098.   524    20.2    20.6    24.9  -0.01794
  27181 15SE-115    115.00  27321 SRAF-115    115.00  1  -29317.   129    23.0    23.1    23.9  -0.00362
  28161 AHUA-230    230.00  29161 F-AHU-AGU   230.00  1  -29362.   396     3.7     3.9     7.2  -0.01335
  28181 15SE-230    230.00  29182 F-15SE-AGC2 230.00  2  -32233.   396     5.5     5.2     2.2   0.01245
  27351 SANA-115    115.00  27381 OPIC-115    115.00  1  -57252.   130    -7.4    -7.3    -6.8  -0.00240
  27281 CHIN-115    115.00  27391 TECO-115    115.00  1  <-99999   130    33.0    33.0    32.8   0.00110
  27321 SRAF-115    115.00  27281 CHIN-115    115.00  1  <-99999   130    33.1    33.1    32.8   0.00110

 Contingency "INTR GUAT MOY" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "INTR GUAT LVG" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "INTR HOND NNC" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "INTR HOND AGC" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "SANA-GUAJ" has 5 bus(es) not connected back to a swing (type 3) bus

 Contingency "SMIG-HAVI" has 5 bus(es) not connected back to a swing (type 3) bus

 Contingency "LUNI-HAVI" has 2 bus(es) not connected back to a swing (type 3) bus

 Contingency "SMAR-SBAR_DOB" has 4 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution
     PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS(R)E     THU, FEB 01 2018  16:39
 SISTEMA ELCTRICO REGIONAL - DEMANDA MAX NOC-2DO SEM18                   PAGE 2
 ESTUDIOS ERT 2018-2019
 *** TLTG IMPORT LIMIT OUTPUT FOR SUBSYSTEM ESAG2                            ***

 SOLUTION OF  52 SYSTEM CONDITIONS ATTEMPTED      0 INSOLUBLE SYSTEM CONDITIONS

   INCR.                                                                    PRE- RATING
   TRANS <----------------- LIMITING ELEMENT ----------------->   DISTR.   SHIFT BAS/CNT
   CAPAB <------- F R O M -------> <--------- T O --------->CKT   FACTOR     MW    A/A  <------------------ CONTINGENCY DESCRIPTION ------------------->
   -91.0  27131 ACAJ-115    115.00  27411 SONS-115    115.00 1  -0.50000    84.5  130.0 CONTINGENCY ACAJ-ATEO
  -148.8  27411 SONS-115    115.00  27441 ATEO-115    115.00 1  -0.39395    71.3  129.9 CONTINGENCY ACAJ-ATEO
  -230.1  27131 ACAJ-115    115.00  27411 SONS-115    115.00 1  -0.32993    54.1  130.0 CONTINGENCY SANT-TALN
  -234.7  27131 ACAJ-115    115.00  27411 SONS-115    115.00 1  -0.31414    56.3  130.0 CONTINGENCY NCUS-ATEO
  -244.1  27131 ACAJ-115    115.00  27411 SONS-115    115.00 1  -0.34739    45.2  130.0 CONTINGENCY ATEO-TALN
  -253.8  27131 ACAJ-115    115.00  27411 SONS-115    115.00 1  -0.31414    50.3  130.0 CONTINGENCY NCUS-STOM
  -254.2  27131 ACAJ-115    115.00  27411 SONS-115    115.00 1  -0.30520    52.4  130.0 CONTINGENCY SMAR-SBAR_DOB
  -258.5  27131 ACAJ-115    115.00  27411 SONS-115    115.00 1  -0.32993    44.7  130.0 CONTINGENCY SANT-NEJA
  -261.4  27131 ACAJ-115    115.00  27411 SONS-115    115.00 1  -0.30448    50.4  130.0 BASE CASE
  -272.8  27131 ACAJ-115    115.00  27411 SONS-115    115.00 1  -0.31414    44.3  130.0 CONTINGENCY SMAR-STOM
  -274.0* 27131 ACAJ-115    115.00  27411 SONS-115    115.00 1  -0.29114    50.2  130.0 CONTINGENCY AHUA-NEJA_DOB
  -282.5  27161 AHUA-115    115.00  27411 SONS-115    115.00 1   0.34518   -30.1  127.6 CONTINGENCY ACAJ-ATEO
  -297.0  27161 AHUA-115    115.00  27411 SONS-115    115.00 1   0.33727   -27.4  127.6 CONTINGENCY OPIC-SONS
     PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS(R)E     THU, FEB 01 2018  16:39
 SISTEMA ELCTRICO REGIONAL - DEMANDA MAX NOC-2DO SEM18                   PAGE 3
 ESTUDIOS ERT 2018-2019
 *** TLTG IMPORT LIMIT OUTPUT FOR SUBSYSTEM ESAG2                            ***

 * MONITORED ELEMENTS OCCURRING     10 OR MORE TIMES

   NO. <----------------- MONITORED ELEMENT ----------------->
 TIMES <------- F R O M -------> <--------- T O ---------> CKT
    14  27131 ACAJ-115    115.00  27411 SONS-115    115.00  1

 Output completed