SISTEMA OPUESTO ACAJUTLA

###################################

 The working case has a largest mismatch of 0.0 MW at bus 14319 [THP-400     400.00]

 These subsystems were specified:
   # <------- SUBSYSTEM LABEL ------>  BUSES    # <------- SUBSYSTEM LABEL ------>  BUSES    # <------- SUBSYSTEM LABEL ------>  BUSES
   1 GUATEMALA                           575    2 ESAG1                                31    3 ESAG2                                23
   4 ELSALVADOR                           27    5 ESA                                  75    6 ELSALVADORM                          73
   7 ACAJUTLA                              8    8 HONDURAS                            334    9 GUA-HON                             909

 Study system generation is         514.7 MW
 Opposing system generation is      187.9 MW
 Study system net interchange is    514.5 MW
     PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS(R)E     THU, FEB 01 2018  16:39
 SISTEMA ELCTRICO REGIONAL - DEMANDA MAX DIU-1ER SEM18                   PAGE 1
 ESTUDIOS ERT2018-2019
 ** TLTG IMPORT LIMIT OUTPUT FOR BASE CASE                                    **

 DISTRIBUTION FACTOR FILE:     G:\control\Estudios\ERT2018\Simulaciones\TLTG\2018-2019\ERT_MaxDiu1Sem18\Dfx_ERT_MaxDiu1Sem18.dfx
 SUBSYSTEM DESCRIPTION FILE:   G:\control\Estudios\ERT2018\Simulaciones\TLTG\2018-2019\subsistemas_TLTG.sub
 MONITORED ELEMENT FILE:       G:\control\Estudios\ERT2018\Simulaciones\TLTG\2018-2019\monitoreo_TLTG.mon
 CONTINGENCY DESCRIPTION FILE: G:\control\Estudios\ERT2018\Simulaciones\TLTG\2018-2019\ESA_TLTG_Cont.con

                                 PRE-SHIFT    DELTA  POST-SHIFT
 STUDY SYSTEM MW GENERATION:        514.7     -20.0     494.7
 OPPOSING SYSTEM MW GENERATION:     187.9      20.0     207.9
 STUDY SYSTEM NET INTERCHANGE:      514.5     -20.0     494.5

 <---------------- STUDY SYSTEM -----------------> <--------------- OPPOSING SYSTEM --------------->
                          <---- GENERATOR MW ---->                          <---- GENERATOR MW ---->
   BUS# X-- NAME --X BASKV    BASE   SHIFT  CHANGE   BUS# X-- NAME --X BASKV    BASE   SHIFT  CHANGE
  20301 SOYA-G1     4.1600    14.8    14.3    -0.6  21136 M1-M3       13.800    36.8    41.1     4.3
  21041 GCSA        13.800    10.8    10.4    -0.4  21137 M4-M6       13.800    36.2    40.5     4.3
  21051 BORE-G1     13.800     7.8     7.5    -0.3  21138 M7-M9       13.800    48.3    52.7     4.4
  21101 5NOV-U1     13.800    15.9    15.3    -0.6  21139 TPTO-G1     13.800    66.6    73.6     7.0
  21104 5NOV-U4     13.800    14.0    13.5    -0.6
  21107 5NOV-U7     13.800    34.5    33.3    -1.2
  21171 CGRA-U1     13.800    76.0    73.3    -2.7
  21181 15SE-U1     13.800    76.0    73.2    -2.8
  21304 TEXT-G1     13.800    25.3    24.4    -0.9
  21371 NEJA-G1     13.800    39.4    37.8    -1.7
  21372 NEJA-G2     13.800    44.4    42.5    -1.9
  21373 NEJA-G3     13.800    49.3    47.2    -2.1
  21451 TEXT-G2     13.800    14.1    13.5    -0.5
  21481 TALN-G1     13.800    46.0    44.3    -1.8
  21482 TALN-G2     13.800    46.3    44.5    -1.8




























































































































































































































































































 LOADINGS AT OR ABOVE 100.0 <------------- BASE CASE ------------->
 OF RATING ARE MARKED WITH '*'                             INCR.          PRE-   POST-   LIMIT
                                                           TRANS RATING  SHIFT   SHIFT    CASE    DISTR.
 <------- F R O M -------> <--------- T O ---------> CKT   CAPAB    A      MW      MW      MW     FACTOR
  27131 ACAJ-115    115.00  27411 SONS-115    115.00  1   -281.4   130    45.0    51.0   130.0* -0.30205
  27161 AHUA-115    115.00  27411 SONS-115    115.00  1   -442.9   127   -21.7   -26.4   -88.9   0.23886
  27132 ACAJ2-115   115.00  27441 ATEO-115    115.00  1   -471.8   260    73.2    81.1   184.6  -0.39590
  27411 SONS-115    115.00  27441 ATEO-115    115.00  1   -489.1   130    42.2    45.8    92.6  -0.17926
  27381 OPIC-115    115.00  27411 SONS-115    115.00  1   -512.7   130   -34.4   -38.1   -86.8   0.18598
  27441 ATEO-115    115.00  27481 TALN-115    115.00  1   -712.9   259   -41.4   -33.0    77.2  -0.42165
  27361 SANT-115    115.00  27481 TALN-115    115.00  1   -893.4   260   -45.4   -50.2  -112.9   0.23987
  28161 AHUA-230    230.00 3WNDTR INTER 2      WND 1  2  -1190.9   148   -20.3   -22.5   -50.4   0.10681
  27381 OPIC-115    115.00  27501 SMAT-115    115.00  1  -1232.3   260    18.1    22.0    73.3  -0.19630
  28161 AHUA-230    230.00 3WNDTR INTER 1      WND 1  1  -1265.4   155   -20.3   -22.5   -50.4   0.10681
  27371 NEJA-115    115.00  27501 SMAT-115    115.00  1  -1348.4   260     4.8     0.9   -50.4   0.19630
  28371 NEJA-230    230.00 3WNDTR NEJA_TR_1    WND 1  1  -2629.0   154    29.6    30.6    42.9  -0.04720
  28371 NEJA-230    230.00 3WNDTR NEJA_TR_2    WND 1  2  -2629.0   154    29.6    30.6    42.9  -0.04720
  28181 15SE-230    230.00 3WNDTR INTER 3      WND 1  1  -2741.7   153   -10.0    -8.8     6.8  -0.05961
  28181 15SE-230    230.00 3WNDTR INTER 4      WND 1  2  -2741.7   153   -10.0    -8.8     6.8  -0.05961
  27161 AHUA-115    115.00  27351 SANA-115    115.00  1  -3437.6   127    40.0    40.5    47.1  -0.02525
  27371 NEJA-115    115.00  27171 CGRA-115    115.00  2  -3464.0   260   -31.8   -30.1    -8.1  -0.08422
  27371 NEJA-115    115.00  27171 CGRA-115    115.00  1  -3464.0   260   -31.8   -30.1    -8.1  -0.08422
  27321 SRAF-115    115.00  27431 SMAR-115    115.00  1  -3891.4   260    47.6    46.0    25.4   0.07894
  28161 AHUA-230    230.00  28371 NEJA-230    230.00  2  -4136.9   396     6.3     8.2    32.8  -0.09419
  28161 AHUA-230    230.00  28371 NEJA-230    230.00  1  -4136.9   396     6.3     8.2    32.8  -0.09419
  27101 5NOV-115    115.00  27321 SRAF-115    115.00  1  -4522.1   260    40.7    39.4    22.0   0.06649
  27351 SANA-115    115.00  27381 OPIC-115    115.00  1  -6164.7   130   -25.7   -25.2   -18.6  -0.02525
  27171 CGRA-115    115.00  27321 SRAF-115    115.00  1  -6846.8   130    17.4    17.0    11.3   0.02152
  28181 15SE-230    230.00  28371 NEJA-230    230.00  2  -8913.4   396    23.3    22.4    10.1   0.04700
  28181 15SE-230    230.00  28371 NEJA-230    230.00  1  -8913.4   396    23.3    22.4    10.1   0.04700
  27181 15SE-115    115.00  27431 SMAR-115    115.00  1  -10233.   130    24.9    24.6    20.7   0.01510
  27181 15SE-115    115.00  27431 SMAR-115    115.00  2  -10233.   130    24.9    24.6    20.7   0.01510
  27181 15SE-115    115.00  27321 SRAF-115    115.00  1  -15889.   129    18.8    18.9    20.8  -0.00696
  28181 15SE-230    230.00  29181 F-15SE-NNC  230.00  1  -32261.   521   -30.9   -31.2   -35.2   0.01518
  28161 AHUA-230    230.00  29162 F-AHU-MOY   230.00  1  -34683.   524    22.6    22.9    26.6  -0.01446
  28161 AHUA-230    230.00  29161 F-AHU-AGU   230.00  1  -36251.   396     5.4     5.7     8.5  -0.01076
  28181 15SE-230    230.00  29182 F-15SE-AGC2 230.00  2  -39820.   396     3.9     3.7     1.1   0.01004
  27321 SRAF-115    115.00  27281 CHIN-115    115.00  1  -61696.   130     0.6     0.6     0.0   0.00211
  27281 CHIN-115    115.00  27391 TECO-115    115.00  1  -76427.   130    31.5    31.5    31.0   0.00211

 Contingency "INTR GUAT MOY" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "INTR GUAT LVG" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "INTR HOND NNC" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "INTR HOND AGC" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "SANA-GUAJ" has 5 bus(es) not connected back to a swing (type 3) bus

 Contingency "SMIG-HAVI" has 5 bus(es) not connected back to a swing (type 3) bus

 Contingency "LUNI-HAVI" has 2 bus(es) not connected back to a swing (type 3) bus

 Contingency "SMAR-SBAR_DOB" has 4 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution
     PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS(R)E     THU, FEB 01 2018  16:39
 SISTEMA ELCTRICO REGIONAL - DEMANDA MAX DIU-1ER SEM18                   PAGE 2
 ESTUDIOS ERT2018-2019
 *** TLTG IMPORT LIMIT OUTPUT FOR SUBSYSTEM ESAG2                            ***

 SOLUTION OF  52 SYSTEM CONDITIONS ATTEMPTED      0 INSOLUBLE SYSTEM CONDITIONS

   INCR.                                                                    PRE- RATING
   TRANS <----------------- LIMITING ELEMENT ----------------->   DISTR.   SHIFT BAS/CNT
   CAPAB <------- F R O M -------> <--------- T O --------->CKT   FACTOR     MW    A/A  <------------------ CONTINGENCY DESCRIPTION ------------------->
   -96.8  27131 ACAJ-115    115.00  27411 SONS-115    115.00 1  -0.50000    81.6  130.0 CONTINGENCY ACAJ-ATEO
  -114.3  27411 SONS-115    115.00  27441 ATEO-115    115.00 1  -0.40386    83.7  129.9 CONTINGENCY ACAJ-ATEO
  -245.7  27131 ACAJ-115    115.00  27411 SONS-115    115.00 1  -0.32688    49.7  130.0 CONTINGENCY SANT-TALN
  -254.4  27131 ACAJ-115    115.00  27411 SONS-115    115.00 1  -0.31072    51.0  130.0 CONTINGENCY NCUS-ATEO
  -258.3  27131 ACAJ-115    115.00  27411 SONS-115    115.00 1  -0.34569    40.7  130.0 CONTINGENCY ATEO-TALN
  -263.7  27161 AHUA-115    115.00  27411 SONS-115    115.00 1   0.33428   -39.3  127.4 CONTINGENCY ACAJ-ATEO
  -274.1  27131 ACAJ-115    115.00  27411 SONS-115    115.00 1  -0.30283    47.0  130.0 CONTINGENCY SMAR-SBAR_DOB
  -276.1  27161 AHUA-115    115.00  27411 SONS-115    115.00 1   0.32522   -37.6  127.4 CONTINGENCY OPIC-SONS
  -276.7  27131 ACAJ-115    115.00  27411 SONS-115    115.00 1  -0.31072    44.0  130.0 CONTINGENCY NCUS-STOM
  -281.4  27131 ACAJ-115    115.00  27411 SONS-115    115.00 1  -0.30205    45.0  130.0 BASE CASE
  -287.6  27131 ACAJ-115    115.00  27411 SONS-115    115.00 1  -0.31072    40.6  130.0 CONTINGENCY SMAR-STOM
  -288.8  27131 ACAJ-115    115.00  27411 SONS-115    115.00 1  -0.32688    35.6  130.0 CONTINGENCY SANT-NEJA
  -297.5* 27131 ACAJ-115    115.00  27411 SONS-115    115.00 1  -0.28873    44.1  130.0 CONTINGENCY AHUA-NEJA_DOB
     PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS(R)E     THU, FEB 01 2018  16:39
 SISTEMA ELCTRICO REGIONAL - DEMANDA MAX DIU-1ER SEM18                   PAGE 3
 ESTUDIOS ERT2018-2019
 *** TLTG IMPORT LIMIT OUTPUT FOR SUBSYSTEM ESAG2                            ***

 * MONITORED ELEMENTS OCCURRING     10 OR MORE TIMES

   NO. <----------------- MONITORED ELEMENT ----------------->
 TIMES <------- F R O M -------> <--------- T O ---------> CKT
    11  27131 ACAJ-115    115.00  27411 SONS-115    115.00  1

 Output completed