SISTEMA OPUESTO ACAJUTLA

###################################

 The working case has a largest mismatch of 0.0 MW at bus 14319 [THP-400     400.00]

 These subsystems were specified:
   # <------- SUBSYSTEM LABEL ------>  BUSES    # <------- SUBSYSTEM LABEL ------>  BUSES    # <------- SUBSYSTEM LABEL ------>  BUSES
   1 GUATEMALA                           575    2 ESAG1                                31    3 ESAG2                                23
   4 ELSALVADOR                           27    5 ESA                                  75    6 ELSALVADORM                          73
   7 ACAJUTLA                              8    8 HONDURAS                            334    9 GUA-HON                             909

 Study system generation is         482.7 MW
 Opposing system generation is      190.9 MW
 Study system net interchange is    482.5 MW
     PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS(R)E     MON, MAY 28 2018  14:21
 SISTEMA ELCTRICO REGIONAL - DEMANDA MAX NOC-1ER SEM19                   PAGE 1
 ESTUDIOS ERT 2018-2019
 ** TLTG IMPORT LIMIT OUTPUT FOR BASE CASE                                    **

 DISTRIBUTION FACTOR FILE:     G:\control\Estudios\ERT2018\Simulaciones\TLTG\2019m\ERT_MaxNoc1Sem19\Dfx_ERT_MaxNoc1Sem19.dfx
 SUBSYSTEM DESCRIPTION FILE:   G:\control\Estudios\ERT2018\Simulaciones\TLTG\2019m\subsistemas_TLTG.sub
 MONITORED ELEMENT FILE:       G:\control\Estudios\ERT2018\Simulaciones\TLTG\2019m\monitoreo_TLTG.mon
 CONTINGENCY DESCRIPTION FILE: G:\control\Estudios\ERT2018\Simulaciones\TLTG\2019m\ESA_TLTG_Cont.con

                                 PRE-SHIFT    DELTA  POST-SHIFT
 STUDY SYSTEM MW GENERATION:        482.7     -20.0     462.7
 OPPOSING SYSTEM MW GENERATION:     190.9      20.0     210.9
 STUDY SYSTEM NET INTERCHANGE:      482.5     -20.0     462.5

 <---------------- STUDY SYSTEM -----------------> <--------------- OPPOSING SYSTEM --------------->
                          <---- GENERATOR MW ---->                          <---- GENERATOR MW ---->
   BUS# X-- NAME --X BASKV    BASE   SHIFT  CHANGE   BUS# X-- NAME --X BASKV    BASE   SHIFT  CHANGE
  20301 SOYA-G1     4.1600    14.8    14.3    -0.5  21136 M1-M3       13.800    38.3    42.6     4.3
  21101 5NOV-U1     13.800    16.4    15.8    -0.5  21137 M4-M6       13.800    37.7    42.0     4.3
  21104 5NOV-U4     13.800    14.5    14.0    -0.5  21138 M7-M9       13.800    48.3    52.7     4.4
  21106 5NOV-U6     13.800    35.0    34.0    -1.1  21139 TPTO-G1     13.800    66.6    73.6     7.0
  21111 GUAJ-U1     13.800    12.0    11.5    -0.5
  21171 CGRA-U1     13.800    50.0    47.6    -2.4
  21172 CGRA-U2     13.800    50.0    47.6    -2.4
  21181 15SE-U1     13.800    45.0    42.5    -2.5
  21182 15SE-U2     13.800    45.0    42.5    -2.5
  21304 TEXT-G1     13.800     6.6     6.4    -0.2
  21371 NEJA-G1     13.800    39.4    38.0    -1.5
  21372 NEJA-G2     13.800    44.4    42.7    -1.7
  21373 NEJA-G3     13.800     3.0     2.8    -0.2
  21451 TEXT-G2     13.800    14.1    13.6    -0.5
  21481 TALN-G1     13.800    46.0    44.5    -1.6
  21482 TALN-G2     13.800    46.3    44.7    -1.6




























































































































































































































































































 LOADINGS AT OR ABOVE 100.0 <------------- BASE CASE ------------->
 OF RATING ARE MARKED WITH '*'                             INCR.          PRE-   POST-   LIMIT
                                                           TRANS RATING  SHIFT   SHIFT    CASE    DISTR.
 <------- F R O M -------> <--------- T O ---------> CKT   CAPAB    A      MW      MW      MW     FACTOR
  27161 AHUA-115    115.00  27411 SONS-115    115.00  1   -417.1   128   -22.9   -27.9  -127.6*  0.25104
  27132 ACAJ2-115   115.00  27441 ATEO-115    115.00  1   -482.4   260    71.8    79.6   234.5  -0.39013
  27131 ACAJ-115    115.00  27411 SONS-115    115.00  1   -518.8   205    46.8    52.9   174.0  -0.30493
  27381 OPIC-115    115.00  27411 SONS-115    115.00  1   -526.9   130   -30.8   -34.5  -109.2   0.18807
  27411 SONS-115    115.00  27441 ATEO-115    115.00  1   -530.7   130    39.3    42.7   110.5  -0.17076
  27441 ATEO-115    115.00  27481 TALN-115    115.00  1   -743.5   259   -49.5   -41.1   123.8  -0.41548
  27361 SANT-115    115.00  27481 TALN-115    115.00  1   -871.9   260   -36.3   -41.5  -143.2   0.25634
  28161 AHUA-230    230.00 3WNDTR INTER 2      WND 1  2  -1184.5   148   -18.2   -20.4   -63.9   0.10959
  28161 AHUA-230    230.00 3WNDTR INTER 1      WND 1  1  -1253.8   156   -18.2   -20.4   -63.9   0.10959
  27381 OPIC-115    115.00  27501 SMAT-115    115.00  1  -1258.7   260    17.2    21.1    97.7  -0.19289
  27371 NEJA-115    115.00  27501 SMAT-115    115.00  1  -1334.1   260    -2.6    -6.5   -83.1   0.19289
  28181 15SE-230    230.00 3WNDTR INTER 3      WND 1  1  -1898.1   153   -11.2    -9.5    24.9  -0.08663
  28181 15SE-230    230.00 3WNDTR INTER 4      WND 1  2  -1898.1   153   -11.2    -9.5    24.9  -0.08663
  27371 NEJA-115    115.00  27171 CGRA-115    115.00  2  -2455.1   260   -37.8   -35.3    12.8  -0.12126
  27371 NEJA-115    115.00  27171 CGRA-115    115.00  1  -2455.1   260   -37.8   -35.3    12.8  -0.12126
  27321 SRAF-115    115.00  27431 SMAR-115    115.00  1  -2857.5   260    51.0    48.8     5.6   0.10874
  27161 AHUA-115    115.00  27351 SANA-115    115.00  1  -3158.6   128    27.6    28.3    40.9  -0.03185
  28161 AHUA-230    230.00  28371 NEJA-230    230.00  1  -4127.2   396     4.8     6.6    44.3  -0.09478
  28161 AHUA-230    230.00  28371 NEJA-230    230.00  2  -4127.2   396     4.8     6.6    44.3  -0.09478
  27101 5NOV-115    115.00  27321 SRAF-115    115.00  1  -4432.3   260    46.6    45.2    17.7   0.06915
  27181 15SE-115    115.00  27431 SMAR-115    115.00  1  -4914.5   130    26.8    26.2    13.5   0.03183
  27181 15SE-115    115.00  27431 SMAR-115    115.00  2  -4914.5   130    26.8    26.2    13.5   0.03183
  27171 CGRA-115    115.00  27321 SRAF-115    115.00  1  -4971.8   130    23.1    22.5    10.3   0.03080
  28371 NEJA-230    230.00 3WNDTR NEJA_TR_1    WND 1  1  -5450.6   154    29.1    29.6    38.7  -0.02296
  28371 NEJA-230    230.00 3WNDTR NEJA_TR_2    WND 1  2  -5450.6   154    29.1    29.6    38.7  -0.02296
  28181 15SE-230    230.00  28371 NEJA-230    230.00  2  -5847.9   396    24.4    22.9    -5.6   0.07182
  28181 15SE-230    230.00  28371 NEJA-230    230.00  1  -5847.9   396    24.4    22.9    -5.6   0.07182
  27181 15SE-115    115.00  27321 SRAF-115    115.00  1  -22188.   129    20.3    20.1    17.4   0.00675
  28181 15SE-230    230.00  29181 F-15SE-NNC  230.00  1  -27488.   521   -30.7   -31.1   -38.1   0.01783
  28161 AHUA-230    230.00  29162 F-AHU-MOY   230.00  1  -29580.   524    22.0    22.3    29.0  -0.01698
  27351 SANA-115    115.00  27381 OPIC-115    115.00  1  -29894.   130   -14.3   -14.2   -12.3  -0.00482
  28161 AHUA-230    230.00  29161 F-AHU-AGU   230.00  1  -30915.   396     5.0     5.2    10.2  -0.01264
  28181 15SE-230    230.00  29182 F-15SE-AGC2 230.00  2  -33923.   396     4.0     3.8    -0.9   0.01179
  27281 CHIN-115    115.00  27391 TECO-115    115.00  1  -46503.   130    34.4    34.5    35.3  -0.00205
  27321 SRAF-115    115.00  27281 CHIN-115    115.00  1  -61724.   130     3.5     3.6     4.4  -0.00205

 Contingency "INTR GUAT MOY" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "INTR GUAT LVG" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "INTR HOND NNC" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "INTR HOND AGC" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "SANA-GUAJ" has 5 bus(es) not connected back to a swing (type 3) bus

 Contingency "SMIG-HAVI" has 5 bus(es) not connected back to a swing (type 3) bus

 Contingency "LUNI-HAVI" has 2 bus(es) not connected back to a swing (type 3) bus

 Contingency "SMAR-SBAR_DOB" has 4 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution
     PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS(R)E     MON, MAY 28 2018  14:21
 SISTEMA ELCTRICO REGIONAL - DEMANDA MAX NOC-1ER SEM19                   PAGE 2
 ESTUDIOS ERT 2018-2019
 *** TLTG IMPORT LIMIT OUTPUT FOR SUBSYSTEM ESAG2                            ***

 SOLUTION OF  52 SYSTEM CONDITIONS ATTEMPTED      0 INSOLUBLE SYSTEM CONDITIONS

   INCR.                                                                    PRE- RATING
   TRANS <----------------- LIMITING ELEMENT ----------------->   DISTR.   SHIFT BAS/CNT
   CAPAB <------- F R O M -------> <--------- T O --------->CKT   FACTOR     MW    A/A  <------------------ CONTINGENCY DESCRIPTION ------------------->
  -127.3  27411 SONS-115    115.00  27441 ATEO-115    115.00 1  -0.39209    80.0  129.9 CONTINGENCY ACAJ-ATEO
  -244.6  27131 ACAJ-115    115.00  27411 SONS-115    115.00 1  -0.50000    82.7  205.0 CONTINGENCY ACAJ-ATEO
  -253.3  27161 AHUA-115    115.00  27411 SONS-115    115.00 1   0.34507   -40.2  127.6 CONTINGENCY ACAJ-ATEO
  -267.2  27161 AHUA-115    115.00  27411 SONS-115    115.00 1   0.33837   -37.2  127.6 CONTINGENCY OPIC-SONS
  -292.3  27161 AHUA-115    115.00  27411 SONS-115    115.00 1   0.32320   -33.1  127.6 CONTINGENCY SANT-TALN

 Output completed