SISTEMA OPUESTO ACAJUTLA

###################################

 The working case has a largest mismatch of 0.0 MW at bus 3961 [TER TON T61013.800]

 These subsystems were specified:
   # <------- SUBSYSTEM LABEL ------>  BUSES    # <------- SUBSYSTEM LABEL ------>  BUSES    # <------- SUBSYSTEM LABEL ------>  BUSES
   1 GUATEMALA                           492    2 ESAG1                                40    3 ESAG2                                26
   4 ACAJUTLA                             14    5 HONDURAS                            401    6 GUA-HON                             893

 Study system generation is         554.0 MW
 Opposing system generation is      280.3 MW
 Study system net interchange is    554.0 MW
1.......................................................................................................
 .             PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS(R)E     THU, MAR 12 2026  15:59      PAGE 1 .
 .                                                                                                     .
 .                    BASE DE DATOS DE EL SALVADOR                                                     .
 .                                                                                                     .
 .          *** TLTG IMPORT LIMIT OUTPUT FOR BASE CASE                                    ***          .
 .......................................................................................................

 DISTRIBUTION FACTOR FILE:     G:\control\Estudios\ERT2026\simu\TLTG\2027\Min_Lluviosa27\dfx_ Min_Lluviosa27.dfx
 SUBSYSTEM DESCRIPTION FILE:   G:\control\Estudios\ERT2026\simu\TLTG\2027\subsistemas_TLTG.sub
 MONITORED ELEMENT FILE:       G:\control\Estudios\ERT2026\simu\TLTG\2027\monitoreo_TLTG.mon
 CONTINGENCY DESCRIPTION FILE: G:\control\Estudios\ERT2026\simu\TLTG\2027\ESA_TLTG_Cont.con

                                 PRE-SHIFT    DELTA  POST-SHIFT
 STUDY SYSTEM MW GENERATION:        554.0     -20.0     534.0
 OPPOSING SYSTEM MW GENERATION:     280.3      20.0     300.3
 STUDY SYSTEM NET INTERCHANGE:      554.0     -20.0     534.0

 <------------------ STUDY SYSTEM ------------------->  <----------------- OPPOSING SYSTEM ----------------->
                              <---- GENERATOR MW ---->                               <---- GENERATOR MW ---->
   BUS#-SCT X-- NAME --X BASKV    BASE   SHIFT  CHANGE    BUS#-SCT X-- NAME --X BASKV    BASE   SHIFT  CHANGE
  21081     3FEB-U1     13.800    33.0    31.9    -1.1   21311     CT EDP-01   13.800    25.9    28.1     2.3
  21082     3FEB-U2     13.800    33.0    31.9    -1.1   21312     CT EDP-02   13.800    57.4    61.9     4.5
  21101     5NOV-U1     13.800    15.0    14.3    -0.7   21313     CT EDP-03   13.800    40.0    43.1     3.1
  21102     5NOV-U2     13.800    15.0    14.3    -0.7   21314     CT EDP-04   13.800    34.9    37.1     2.3
  21103     5NOV-U3     13.800    15.0    14.3    -0.7   21315     CT EDP-05   13.800    52.3    55.7     3.4
  21105     5NOV-U5     13.800    15.5    14.8    -0.7   21316     CT EDP-06   13.800    69.8    74.3     4.5
  21106     5NOV-U6     13.800    32.5    31.2    -1.3
  21107     5NOV-U7     13.800    32.5    31.2    -1.3
  21111     GUAJ-U1     13.800    15.0    14.3    -0.7
  21171     CGRA-U1     13.800    83.8    80.9    -2.9
  21172     CGRA-U2     13.800    83.8    80.9    -2.9
  21181     15SE-U1     13.800    90.0    87.0    -3.0
  21182     15SE-U2     13.800    90.0    87.0    -3.0

 LOADINGS AT OR ABOVE 100.0 %                                               <------------- BASE CASE ------------->
 OF RATING ARE MARKED WITH '*'                                        INCR.          PRE-   POST-   LIMIT
                                                                      TRANS RATING  SHIFT   SHIFT    CASE    DISTR.
 <--------- F R O M --------->   <----------- T O ----------->  CKT   CAPAB    1      MW      MW      MW     FACTOR
  28371     NEJA-230    230.00   3WNDTR NEJA_TR_2        WND 1   2   -663.7   153    80.0    82.2   153.2* -0.11026
  28161     AHUA-230    230.00    28311     EDP-230     230.00   2   -735.9   295   -59.2   -65.6  -272.2   0.32090
  27131     ACAJ-115    115.00    27411     SONS-115    115.00   2   -769.6   109    34.5    36.4    98.7  -0.09682
  27161     AHUA-115    115.00    27351     SANA-115    115.00   1   -846.1   128    56.1    57.9   112.9  -0.08550
  28312     EDP2-230    230.00   3WNDTR EDP_TR230        WND 1   2   -934.2   250    81.5    85.1   201.1  -0.18026

  27381     OPIC-115    115.00    27411     SONS-115    115.00   1   -950.0   130   -32.9   -35.0  -100.7   0.10215
  27132     ACAJ2-115   115.00    27441     ATEO-115    115.00   1  -1172.9   260    66.9    70.2   176.1  -0.16456
  28181     15SE-230    230.00   3WNDTR INTER 4          WND 1   2  -1192.7   154   -42.0   -38.7    67.3  -0.16465
  28161     AHUA-230    230.00    28371     NEJA-230    230.00   2  -1483.7   396    33.5    38.4   195.6  -0.24433
  27411     SONS-115    115.00    27441     ATEO-115    115.00   1  -1644.4   205    43.8    45.8   108.8  -0.09797

  27441     ATEO-115    115.00    27551     VOLC-115    115.00   1  -1658.5   260    21.4    24.3   116.9  -0.14386
  27371     NEJA-115    115.00    27561     APOP-115    115.00   1  -1741.2   260   -74.0   -70.2    53.3  -0.19185
  27381     OPIC-115    115.00    27501     SMAT-115    115.00   1  -1741.5   260    -9.4    -6.3    93.2  -0.15458
  27361     SANT-115    115.00    27551     VOLC-115    115.00   1  -1765.3   260    44.1    40.7   -70.2   0.17221
  27081     3FEB-115    115.00    27181     15SE-115    115.00   1  -1771.5   128    63.9    61.7    -7.9   0.10819

  27171     CGRA-115    115.00    27371     NEJA-115    115.00   1  -1805.7   260    86.5    82.7   -40.8   0.19185
  27171     CGRA-115    115.00    27561     APOP-115    115.00   1  -1811.6   260    87.7    83.9   -39.6   0.19185
  27371     NEJA-115    115.00    27501     SMAT-115    115.00   1  -1905.8   260    34.8    31.7   -67.8   0.15459
  27321     SRAF-115    115.00    27431     SMAR-115    115.00   1  -2031.4   260    88.3    84.9   -25.4   0.17131
  27361     SANT-115    115.00    27371     NEJA-115    115.00   1  -2144.2   260  -109.3  -105.8     5.0  -0.17221

  27421     NCUS-115    115.00    27551     VOLC-115    115.00   1  -2188.3   260   -62.1   -63.9  -122.0   0.09032
  27101     5NOV-115    115.00    27171     CGRA-115    115.00   1  -2324.2   260    47.5    44.8   -40.2   0.13218
  27351     SANA-115    115.00    27381     OPIC-115    115.00   1  -2409.8   130     3.6     4.7    38.4  -0.05244
  27101     5NOV-115    115.00    27321     SRAF-115    115.00   1  -2455.7   260    78.0    75.3   -13.3   0.13754
  27371     NEJA-115    115.00    27431     SMAR-115    115.00   1  -2653.8   260    16.0    17.8    77.0  -0.09193

  27421     NCUS-115    115.00    27461     STOM-115    115.00   1  -2837.1   260     3.7     5.5    63.7  -0.09032
  27301     SOYA-115    115.00    27371     NEJA-115    115.00   1  -2884.9   259   -52.5   -54.0  -100.1   0.07169
  28161     AHUA-230    230.00   3WNDTR INTER 2          WND 1   2  -3052.9   154    13.7    14.6    44.2  -0.04598
  27441     ATEO-115    115.00    27481     TALN-115    115.00   1  -3196.2   410    30.7    33.1   109.5  -0.11867
  28181     15SE-230    230.00    28371     NEJA-230    230.00   2  -3299.1   396    46.6    44.0   -42.3   0.13407

  27481     TALN-115    115.00    27551     VOLC-115    115.00   1  -3317.3   410    16.3    18.7    95.1  -0.11867
  27431     SMAR-115    115.00    27461     STOM-115    115.00   1  -3814.1   260    84.8    82.9    24.8   0.09032
  27301     SOYA-115    115.00    27431     SMAR-115    115.00   1  -3967.5   260   -24.5   -23.1    23.1  -0.07169
  27111     GUAJ-115    115.00    27351     SANA-115    115.00   1  -4036.0   130     3.4     2.8   -18.5   0.03306
  27181     15SE-115    115.00    27431     SMAR-115    115.00   2  -4286.1   130    47.4    46.6    20.0   0.04131

  27171     CGRA-115    115.00    27321     SRAF-115    115.00   1  -4389.3   130    32.3    31.6     7.8   0.03699
  28181     15SE-230    230.00    29181     F-15SE-NNC  230.00   1  -13960.   521    -5.9    -6.7   -30.4   0.03689
  28161     AHUA-230    230.00    29162     F-AHU-MOY   230.00   1  -14299.   524    19.7    20.4    43.1  -0.03529
  28161     AHUA-230    230.00    29161     F-AHU-LVG   230.00   1  -15140.   396     3.9     4.5    21.1  -0.02588
  27161     AHUA-115    115.00    27411     SONS-115    115.00   1  -15212.   128    29.9    30.0    34.2  -0.00647

  28181     15SE-230    230.00    29182     F-15SE-AGC  230.00   2  -16149.   396    -3.9    -4.4   -20.0   0.02428
  27181     15SE-115    115.00    27321     SRAF-115    115.00   1  -38017.   130    36.0    36.0    37.6  -0.00246
  27071     LANG-115    115.00    27371     NEJA-115    115.00   1  <-99999   130     0.0     0.0     0.0  -0.00000
  27111     GUAJ-115    115.00    27241     VENT-115    115.00   1  <-99999   130   -10.9   -10.9   -10.9  -0.00000
  27131     ACAJ-115    115.00    27132     ACAJ2-115   115.00   1  <-99999  NONE   -78.1   -81.9  -206.6   0.19365

  27131     ACAJ-115    115.00    27221     ALVA-115    115.00   1  <-99999   125     0.0     0.0     0.0   0.00000
  27132     ACAJ2-115   115.00    27133     TPTO-115    115.00   1  <-99999   110    -0.0    -0.0    -0.0  -0.00000
  27171     CGRA-115    115.00    27531     CHAL-115    115.00   1  <-99999   130     0.0     0.0     0.0   0.00000
  27181     15SE-115    115.00    27211     BERL-115    115.00   1  <-99999   130   -37.0   -37.0   -36.8  -0.00031
  27181     15SE-115    115.00    27341     SMIG-115    115.00   1  <-99999   130    54.5    54.5    54.8  -0.00044

  27201     ANTA-115    115.00    27471     PEDR-115    115.00   1  <-99999    75     0.0     0.0     0.0   0.00000
  27211     BERL-115    115.00    27341     SMIG-115    115.00   1  <-99999   130    67.9    67.9    68.1  -0.00031
  27281     CHIN-115    115.00    27291     JIBO-115    115.00   1  <-99999   130     0.0     0.0     0.0   0.00000
  27281     CHIN-115    115.00    27321     SRAF-115    115.00   1  <-99999   130   -29.5   -29.5   -29.0  -0.00075
  27281     CHIN-115    115.00    27391     TECO-115    115.00   1  <-99999   130    29.4    29.4    28.9   0.00075

  27341     SMIG-115    115.00    27401     OZAT-115    115.00   1  <-99999   130    15.6    15.6    16.1  -0.00075
  27341     SMIG-115    115.00    27511     HAVI-115    115.00   1  <-99999   260    34.4    34.4    34.4   0.00000
  27371     NEJA-115    115.00    27372     NEPO-115    115.00   1  <-99999  NONE     0.0     0.0     0.0   0.00000
  27391     TECO-115    115.00    27401     OZAT-115    115.00   1  <-99999   130     9.3     9.2     8.8   0.00075
  27401     OZAT-115    115.00    27402     CAPE115-FV  115.00   1  <-99999  NONE     0.0     0.0     0.0   0.00000

  27431     SMAR-115    115.00    27451     SBAR-115    115.00   2  <-99999   129    40.5    40.5    40.5   0.00000
  27461     STOM-115    115.00    27471     PEDR-115    115.00   1  <-99999   130    38.9    38.9    38.9   0.00000
  27491     LUNI-115    115.00    27511     HAVI-115    115.00   1  <-99999   260   -34.2   -34.2   -34.2  -0.00000
  27511     HAVI-115    115.00    27521     CHAP-115    115.00   1  <-99999   130     0.0     0.0     0.0   0.00000

 Contingency "INTR_GUAT_MOY" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "INTR_GUAT_LVG" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "INTR_HOND_NNC" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "INTR_HOND_AGC" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "STOM-PEDR" has 8 bus(es) not connected back to a swing (type 3) bus

 Contingency "SANA-GUAJ" has 8 bus(es) not connected back to a swing (type 3) bus

 Contingency "SMIG-HAVI" has 8 bus(es) not connected back to a swing (type 3) bus

 Contingency "LUNI-HAVI" has 5 bus(es) not connected back to a swing (type 3) bus

 Contingency "SMAR-SBAR_DOB" has 4 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution
1.......................................................................................................................................................
 .                                     PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS(R)E     THU, MAR 12 2026  15:59                              PAGE 2 .
 .                                                                                                                                                     .
 .                                            BASE DE DATOS DE EL SALVADOR                                                                             .
 .                                                                                                                                                     .
 .                                   *** TLTG IMPORT LIMIT OUTPUT FOR SUBSYSTEM ESAG2                            ***                                   .
 .......................................................................................................................................................

 SOLUTION OF  59 SYSTEM CONDITIONS ATTEMPTED      0 INSOLUBLE SYSTEM CONDITIONS

   INCR.                                                                            PRE- RATING
   TRANS <--------------------- LIMITING ELEMENT --------------------->   DISTR.   SHIFT BAS/CNT
   CAPAB <--------- F R O M ---------> <----------- T O ----------->CKT   FACTOR     MW    1/1  <------------------ CONTINGENCY DESCRIPTION ------------------->
  -109.2  27131     ACAJ-115    115.00  27411     SONS-115    115.00 2  -0.31447    74.6  109.0 CONTINGENCY EDP-AHUA_DOB
  -152.8  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.17440   126.5  153.2 CONTINGENCY NEJA_AUTOTF1
  -216.2  28312     EDP2-230    230.00 3WNDTR EDP_TR230        WND 1 2  -0.50325   141.0  249.9 CONTINGENCY EDP-AHUA_DOB
  -325.8  27161     AHUA-115    115.00  27351     SANA-115    115.00 1  -0.18162    69.3  128.5 CONTINGENCY AHUA-NEJA_DOB
  -336.6  28312     EDP2-230    230.00 3WNDTR EDP_TR230        WND 1 2  -0.31694   143.2  249.9 CONTINGENCY EDP_AUTOTF1
  -344.1  28161     AHUA-230    230.00  28311     EDP-230     230.00 2   0.55879  -103.1  295.3 CONTINGENCY EDP-AHUA-1
  -372.4  27161     AHUA-115    115.00  27411     SONS-115    115.00 1   0.28188   -23.3  128.3 CONTINGENCY EDP-AHUA_DOB
  -383.1  27381     OPIC-115    115.00  27411     SONS-115    115.00 1   0.20418   -51.8  130.0 CONTINGENCY EDP-AHUA_DOB
  -413.6  27131     ACAJ-115    115.00  27411     SONS-115    115.00 2  -0.14146    50.5  109.0 CONTINGENCY ACAJ-SONS
  -417.5  27132     ACAJ2-115   115.00  27441     ATEO-115    115.00 1  -0.37105   105.0  259.9 CONTINGENCY EDP-AHUA_DOB
  -421.9  27131     ACAJ-115    115.00  27411     SONS-115    115.00 2  -0.13745    51.0  109.0 CONTINGENCY ACAJ-ATEO
  -447.2  27381     OPIC-115    115.00  27411     SONS-115    115.00 1   0.19005   -45.0  130.0 CONTINGENCY AHUA-NEJA_DOB
  -451.4  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.13753    91.1  153.2 CONTINGENCY ACAJ-ATEO
  -455.6  27131     ACAJ-115    115.00  27411     SONS-115    115.00 2  -0.14812    41.5  109.0 CONTINGENCY AHUA-NEJA_DOB
  -482.4  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.12781    91.5  153.2 CONTINGENCY AHUA-SANA
  -507.3  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.14885    77.7  153.2 CONTINGENCY SMAT-OPIC
  -511.8  28312     EDP2-230    230.00 3WNDTR EDP_TR230        WND 1 2  -0.29761    97.5  249.9 CONTINGENCY AHUA-NEJA_DOB
  -515.4  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.20783    46.1  153.2 CONTINGENCY NEJA-15SE_DOB
  -542.0  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.12577    85.0  153.2 CONTINGENCY OPIC-SONS
  -549.9  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.14885    71.3  153.2 CONTINGENCY NEJA-SMAT
  -554.4  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.08995   103.3  153.2 CONTINGENCY 15SE-SMAR_DOB
  -554.7  27131     ACAJ-115    115.00  27411     SONS-115    115.00 2  -0.12497    39.7  109.0 CONTINGENCY EDP-AHUA-1
  -555.5  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.12215    85.3  153.2 CONTINGENCY SONS-ATEO
  -563.9  27161     AHUA-115    115.00  27351     SANA-115    115.00 1  -0.11272    64.9  128.5 CONTINGENCY OPIC-SONS
  -585.7* 28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.13636    73.3  153.2 CONTINGENCY VOLC-SANT
  -593.3  27132     ACAJ2-115   115.00  27441     ATEO-115    115.00 1  -0.29513    84.8  259.9 CONTINGENCY AHUA-NEJA_DOB
  -598.0  27381     OPIC-115    115.00  27411     SONS-115    115.00 1   0.13080   -51.8  130.0 CONTINGENCY AHUA-SANA
  -604.6  28161     AHUA-230    230.00  28311     EDP-230     230.00 2   0.36255   -76.1  295.3 CONTINGENCY ACAJ-ATEO
  -635.4  27161     AHUA-115    115.00  27351     SANA-115    115.00 1  -0.10882    59.3  128.5 CONTINGENCY AHUA-NEJA-1
  -664.1  28161     AHUA-230    230.00  28311     EDP-230     230.00 2   0.34153   -68.5  295.3 CONTINGENCY EDP_AUTOTF1
  -666.1  27131     ACAJ-115    115.00  27411     SONS-115    115.00 2  -0.09872    43.2  109.0 CONTINGENCY AHUA-SONS
  -666.3  27131     ACAJ-115    115.00  27411     SONS-115    115.00 2  -0.10927    36.2  109.0 CONTINGENCY AHUA-NEJA-1
  -678.2  28161     AHUA-230    230.00  28311     EDP-230     230.00 2   0.33874   -65.6  295.3 CONTINGENCY ACAJ-SONS
  -684.5  28161     AHUA-230    230.00  28311     EDP-230     230.00 2   0.33726   -64.5  295.3 CONTINGENCY OPIC-SONS
1....................................................................................................
 .           PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS(R)E     THU, MAR 12 2026  15:59     PAGE 3 .
 .                                                                                                  .
 .                   BASE DE DATOS DE EL SALVADOR                                                   .
 .                                                                                                  .
 .         *** TLTG IMPORT LIMIT OUTPUT FOR SUBSYSTEM ESAG2                            ***          .
 ....................................................................................................

 * MONITORED ELEMENTS OCCURRING     10 OR MORE TIMES

   NO. <--------------------- MONITORED ELEMENT --------------------->
 TIMES <--------- F R O M ---------> <----------- T O -----------> CKT
    38  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1  2

 Output completed