SISTEMA OPUESTO ACAJUTLA

###################################

 The working case has a largest mismatch of 0.0 MW at bus 3961 [TER TON T61013.800]

 These subsystems were specified:
   # <------- SUBSYSTEM LABEL ------>  BUSES    # <------- SUBSYSTEM LABEL ------>  BUSES    # <------- SUBSYSTEM LABEL ------>  BUSES
   1 GUATEMALA                           492    2 ESAG1                                40    3 ESAG2                                26
   4 ACAJUTLA                             14    5 HONDURAS                            401    6 GUA-HON                             893

 Study system generation is         554.0 MW
 Opposing system generation is      136.3 MW
 Study system net interchange is    554.0 MW
1.......................................................................................................
 .             PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS(R)E     THU, MAR 12 2026  15:59      PAGE 1 .
 .                                                                                                     .
 .                    BASE DE DATOS DE EL SALVADOR                                                     .
 .                                                                                                     .
 .          *** TLTG IMPORT LIMIT OUTPUT FOR BASE CASE                                    ***          .
 .......................................................................................................

 DISTRIBUTION FACTOR FILE:     G:\control\Estudios\ERT2026\simu\TLTG\2027\Med_Lluviosa27\dfx_ Med_Lluviosa27.dfx
 SUBSYSTEM DESCRIPTION FILE:   G:\control\Estudios\ERT2026\simu\TLTG\2027\subsistemas_TLTG.sub
 MONITORED ELEMENT FILE:       G:\control\Estudios\ERT2026\simu\TLTG\2027\monitoreo_TLTG.mon
 CONTINGENCY DESCRIPTION FILE: G:\control\Estudios\ERT2026\simu\TLTG\2027\ESA_TLTG_Cont.con

                                 PRE-SHIFT    DELTA  POST-SHIFT
 STUDY SYSTEM MW GENERATION:        554.0     -20.0     534.0
 OPPOSING SYSTEM MW GENERATION:     136.3      20.0     156.3
 STUDY SYSTEM NET INTERCHANGE:      554.0     -20.0     534.0

 <------------------ STUDY SYSTEM ------------------->  <----------------- OPPOSING SYSTEM ----------------->
                              <---- GENERATOR MW ---->                               <---- GENERATOR MW ---->
   BUS#-SCT X-- NAME --X BASKV    BASE   SHIFT  CHANGE    BUS#-SCT X-- NAME --X BASKV    BASE   SHIFT  CHANGE
  21081     3FEB-U1     13.800    33.0    31.9    -1.1   21311     CT EDP-01   13.800    17.4    19.9     2.5
  21082     3FEB-U2     13.800    33.0    31.9    -1.1   21312     CT EDP-02   13.800    17.4    19.9     2.5
  21101     5NOV-U1     13.800    15.0    14.3    -0.7   21314     CT EDP-04   13.800    17.4    19.9     2.5
  21102     5NOV-U2     13.800    15.0    14.3    -0.7   21315     CT EDP-05   13.800    16.2    18.7     2.5
  21103     5NOV-U3     13.800    15.0    14.3    -0.7   21316     CT EDP-06   13.800    67.8    77.8    10.0
  21105     5NOV-U5     13.800    15.5    14.8    -0.7
  21106     5NOV-U6     13.800    32.5    31.2    -1.3
  21107     5NOV-U7     13.800    32.5    31.2    -1.3
  21111     GUAJ-U1     13.800    15.0    14.3    -0.7
  21171     CGRA-U1     13.800    83.8    80.9    -2.9
  21172     CGRA-U2     13.800    83.8    80.9    -2.9
  21181     15SE-U1     13.800    90.0    87.0    -3.0
  21182     15SE-U2     13.800    90.0    87.0    -3.0

 LOADINGS AT OR ABOVE 100.0 %                                               <------------- BASE CASE ------------->
 OF RATING ARE MARKED WITH '*'                                        INCR.          PRE-   POST-   LIMIT
                                                                      TRANS RATING  SHIFT   SHIFT    CASE    DISTR.
 <--------- F R O M --------->   <----------- T O ----------->  CKT   CAPAB    1      MW      MW      MW     FACTOR
  28371     NEJA-230    230.00   3WNDTR NEJA_TR_2        WND 1   2   -631.2   154    84.0    86.2   153.6* -0.11026
  28161     AHUA-230    230.00    28311     EDP-230     230.00   2   -833.0   296   -28.3   -34.7  -230.8   0.32090
  27131     ACAJ-115    115.00    27411     SONS-115    115.00   2   -859.1   109    25.8    27.8    86.9  -0.09682
  27381     OPIC-115    115.00    27411     SONS-115    115.00   1  -1078.5   130   -19.8   -21.9   -84.3   0.10215
  28312     EDP2-230    230.00   3WNDTR EDP_TR230        WND 1   2  -1163.6   250    40.2    43.8   154.0  -0.18026

  27161     AHUA-115    115.00    27351     SANA-115    115.00   1  -1176.7   128    27.5    29.3    81.5  -0.08550
  27132     ACAJ2-115   115.00    27441     ATEO-115    115.00   1  -1238.1   260    56.3    59.6   160.1  -0.16456
  28181     15SE-230    230.00   3WNDTR INTER 4          WND 1   2  -1314.4   153   -63.0   -59.7    41.0  -0.16466
  28161     AHUA-230    230.00    28371     NEJA-230    230.00   2  -1601.9   396     4.6     9.5   158.8  -0.24433
  27441     ATEO-115    115.00    27551     VOLC-115    115.00   1  -1606.0   260    28.9    31.7   119.7  -0.14386

  27381     OPIC-115    115.00    27501     SMAT-115    115.00   1  -1662.1   259     2.3     5.4    99.8  -0.15458
  27411     SONS-115    115.00    27441     ATEO-115    115.00   1  -1690.2   205    39.4    41.4   101.2  -0.09797
  27361     SANT-115    115.00    27551     VOLC-115    115.00   1  -1735.9   256    43.0    39.5   -65.7   0.17221
  27081     3FEB-115    115.00    27181     15SE-115    115.00   1  -1772.2   128    63.9    61.7    -4.4   0.10819
  27371     NEJA-115    115.00    27561     APOP-115    115.00   1  -1789.3   260   -83.3   -79.5    37.8  -0.19185

  27371     NEJA-115    115.00    27501     SMAT-115    115.00   1  -1810.5   259    20.4    17.3   -77.2   0.15458
  27171     CGRA-115    115.00    27371     NEJA-115    115.00   1  -1860.1   260    96.9    93.1   -24.2   0.19185
  27171     CGRA-115    115.00    27561     APOP-115    115.00   1  -1866.2   260    98.1    94.3   -23.0   0.19185
  27351     SANA-115    115.00    27381     OPIC-115    115.00   1  -2062.5   130    21.4    22.4    54.5  -0.05244
  27421     NCUS-115    115.00    27551     VOLC-115    115.00   1  -2148.6   258   -63.8   -65.6  -120.8   0.09032

  27321     SRAF-115    115.00    27431     SMAR-115    115.00   1  -2221.6   260   120.6   117.2    12.5   0.17131
  27101     5NOV-115    115.00    27321     SRAF-115    115.00   1  -2371.5   260    66.6    63.8   -20.2   0.13754
  27101     5NOV-115    115.00    27171     CGRA-115    115.00   1  -2411.0   260    58.9    56.3   -24.5   0.13218
  27361     SANT-115    115.00    27371     NEJA-115    115.00   1  -2531.5   260  -176.4  -172.9   -67.7  -0.17221
  27301     SOYA-115    115.00    27371     NEJA-115    115.00   1  -2634.6   258   -69.6   -71.0  -114.8   0.07169

  27371     NEJA-115    115.00    27431     SMAR-115    115.00   1  -2787.7   260     3.6     5.5    61.6  -0.09193
  27421     NCUS-115    115.00    27461     STOM-115    115.00   1  -3154.8   260   -24.9   -23.1    32.1  -0.09032
  27441     ATEO-115    115.00    27481     TALN-115    115.00   1  -3199.6   409    29.1    31.5   104.0  -0.11867
  27481     TALN-115    115.00    27551     VOLC-115    115.00   1  -3257.8   410    23.3    25.6    98.2  -0.11867
  28161     AHUA-230    230.00   3WNDTR INTER 2          WND 1   2  -3360.9   154    -0.4     0.5    28.7  -0.04598

  28181     15SE-230    230.00    28371     NEJA-230    230.00   2  -3544.7   396    79.4    76.7    -5.2   0.13407
  27431     SMAR-115    115.00    27461     STOM-115    115.00   1  -3873.7   256    94.3    92.5    37.3   0.09032
  27171     CGRA-115    115.00    27321     SRAF-115    115.00   1  -4051.1   130    19.9    19.1    -3.5   0.03699
  27111     GUAJ-115    115.00    27351     SANA-115    115.00   1  -4373.4   130    14.7    14.0    -6.2   0.03306
  27301     SOYA-115    115.00    27431     SMAR-115    115.00   1  -4442.6   260   -58.8   -57.4   -13.6  -0.07169

  27181     15SE-115    115.00    27431     SMAR-115    115.00   2  -4667.7   130    63.0    62.2    36.9   0.04131
  28181     15SE-230    230.00    29181     F-15SE-NNC  230.00   1  -13201.   521   -33.8   -34.5   -57.1   0.03690
  28161     AHUA-230    230.00    29162     F-AHU-MOY   230.00   1  -13990.   525    30.9    31.6    53.2  -0.03530
  28161     AHUA-230    230.00    29161     F-AHU-LVG   230.00   1  -14642.   396    17.0    17.5    33.3  -0.02588
  27161     AHUA-115    115.00    27411     SONS-115    115.00   1  -15758.   129    26.7    26.9    30.8  -0.00647

  28181     15SE-230    230.00    29182     F-15SE-AGC  230.00   2  -16281.   396    -0.6    -1.1   -16.0   0.02428
  27181     15SE-115    115.00    27321     SRAF-115    115.00   1  -33941.   130    46.1    46.1    47.6  -0.00246
  27071     LANG-115    115.00    27371     NEJA-115    115.00   1  <-99999   130     0.0     0.0     0.0  -0.00000
  27111     GUAJ-115    115.00    27241     VENT-115    115.00   1  <-99999   130   -17.5   -17.5   -17.5  -0.00000
  27131     ACAJ-115    115.00    27132     ACAJ2-115   115.00   1  <-99999  NONE   -10.4   -14.3  -132.6   0.19365

  27131     ACAJ-115    115.00    27221     ALVA-115    115.00   1  <-99999   125   -51.0   -51.0   -51.0   0.00000
  27132     ACAJ2-115   115.00    27133     TPTO-115    115.00   1  <-99999   110    -0.0    -0.0    -0.0  -0.00000
  27171     CGRA-115    115.00    27531     CHAL-115    115.00   1  <-99999   130     0.0     0.0     0.0   0.00000
  27181     15SE-115    115.00    27211     BERL-115    115.00   1  <-99999   130   -65.6   -65.6   -65.4  -0.00031
  27181     15SE-115    115.00    27341     SMIG-115    115.00   1  <-99999   129    13.1    13.1    13.3  -0.00044

  27201     ANTA-115    115.00    27471     PEDR-115    115.00   1  <-99999    75    27.7    27.7    27.7   0.00000
  27211     BERL-115    115.00    27341     SMIG-115    115.00   1  <-99999   130    38.8    38.8    39.0  -0.00031
  27281     CHIN-115    115.00    27291     JIBO-115    115.00   1  <-99999   130    -3.3    -3.3    -3.3   0.00000
  27281     CHIN-115    115.00    27321     SRAF-115    115.00   1  <-99999   130    22.2    22.2    22.6  -0.00075
  27281     CHIN-115    115.00    27391     TECO-115    115.00   1  <-99999   130   -18.9   -18.9   -19.4   0.00075

  27341     SMIG-115    115.00    27401     OZAT-115    115.00   1  <-99999   130   -20.8   -20.8   -20.3  -0.00075
  27341     SMIG-115    115.00    27511     HAVI-115    115.00   1  <-99999   260     9.5     9.5     9.5   0.00000
  27371     NEJA-115    115.00    27372     NEPO-115    115.00   1  <-99999  NONE     0.0     0.0     0.0   0.00000
  27391     TECO-115    115.00    27401     OZAT-115    115.00   1  <-99999   130   -43.1   -43.1   -43.6   0.00075
  27401     OZAT-115    115.00    27402     CAPE115-FV  115.00   1  <-99999  NONE   -87.0   -87.0   -87.0   0.00000

  27431     SMAR-115    115.00    27451     SBAR-115    115.00   2  <-99999   128    43.3    43.3    43.3   0.00000
  27461     STOM-115    115.00    27471     PEDR-115    115.00   1  <-99999   126    -7.9    -7.9    -7.9   0.00000
  27491     LUNI-115    115.00    27511     HAVI-115    115.00   1  <-99999   260    -9.4    -9.4    -9.4  -0.00000
  27511     HAVI-115    115.00    27521     CHAP-115    115.00   1  <-99999   130     0.0     0.0     0.0   0.00000

 Contingency "INTR_GUAT_MOY" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "INTR_GUAT_LVG" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "INTR_HOND_NNC" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "INTR_HOND_AGC" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "STOM-PEDR" has 8 bus(es) not connected back to a swing (type 3) bus

 Contingency "SANA-GUAJ" has 8 bus(es) not connected back to a swing (type 3) bus

 Contingency "SMIG-HAVI" has 8 bus(es) not connected back to a swing (type 3) bus

 Contingency "LUNI-HAVI" has 5 bus(es) not connected back to a swing (type 3) bus

 Contingency "SMAR-SBAR_DOB" has 4 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution
1.......................................................................................................................................................
 .                                     PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS(R)E     THU, MAR 12 2026  15:59                              PAGE 2 .
 .                                                                                                                                                     .
 .                                            BASE DE DATOS DE EL SALVADOR                                                                             .
 .                                                                                                                                                     .
 .                                   *** TLTG IMPORT LIMIT OUTPUT FOR SUBSYSTEM ESAG2                            ***                                   .
 .......................................................................................................................................................

 SOLUTION OF  59 SYSTEM CONDITIONS ATTEMPTED      0 INSOLUBLE SYSTEM CONDITIONS

   INCR.                                                                            PRE- RATING
   TRANS <--------------------- LIMITING ELEMENT --------------------->   DISTR.   SHIFT BAS/CNT
   CAPAB <--------- F R O M ---------> <----------- T O ----------->CKT   FACTOR     MW    1/1  <------------------ CONTINGENCY DESCRIPTION ------------------->
  -118.9  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.17440   132.9  153.6 CONTINGENCY NEJA_AUTOTF1
  -203.6  27131     ACAJ-115    115.00  27411     SONS-115    115.00 2  -0.31447    45.0  109.0 CONTINGENCY EDP-AHUA_DOB
  -360.3  28312     EDP2-230    230.00 3WNDTR EDP_TR230        WND 1 2  -0.50325    68.6  249.9 CONTINGENCY EDP-AHUA_DOB
  -429.4  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.08995   115.0  153.6 CONTINGENCY 15SE-SMAR_DOB
  -438.2  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.13753    93.3  153.6 CONTINGENCY ACAJ-ATEO
  -440.9  28161     AHUA-230    230.00  28311     EDP-230     230.00 2   0.55879   -49.2  295.6 CONTINGENCY EDP-AHUA-1
  -461.4  27161     AHUA-115    115.00  27411     SONS-115    115.00 1   0.28188     1.4  128.7 CONTINGENCY EDP-AHUA_DOB
  -463.8  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.14885    84.6  153.6 CONTINGENCY SMAT-OPIC
  -495.5  27381     OPIC-115    115.00  27411     SONS-115    115.00 1   0.20418   -28.8  130.0 CONTINGENCY EDP-AHUA_DOB
  -500.1  27132     ACAJ2-115   115.00  27441     ATEO-115    115.00 1  -0.37105    74.4  260.0 CONTINGENCY EDP-AHUA_DOB
  -500.3  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.12781    89.7  153.6 CONTINGENCY AHUA-SANA
  -501.8  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.14885    78.9  153.6 CONTINGENCY NEJA-SMAT
  -503.4  27131     ACAJ-115    115.00  27411     SONS-115    115.00 2  -0.14146    37.8  109.0 CONTINGENCY ACAJ-SONS
  -504.1  27131     ACAJ-115    115.00  27411     SONS-115    115.00 2  -0.13745    39.7  109.0 CONTINGENCY ACAJ-ATEO
  -529.4  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.12577    87.0  153.6 CONTINGENCY OPIC-SONS
  -530.6  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.12215    88.8  153.6 CONTINGENCY SONS-ATEO
  -538.8  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.12102    88.4  153.6 CONTINGENCY SANA-OPIC
  -544.0  27161     AHUA-115    115.00  27351     SANA-115    115.00 1  -0.18162    29.4  128.2 CONTINGENCY AHUA-NEJA_DOB
  -547.6* 28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.11074    93.0  153.6 CONTINGENCY 15SE-SRAF
  -555.0  27131     ACAJ-115    115.00  27411     SONS-115    115.00 2  -0.14812    26.8  109.0 CONTINGENCY AHUA-NEJA_DOB
  -565.7  28312     EDP2-230    230.00 3WNDTR EDP_TR230        WND 1 2  -0.31694    70.6  249.9 CONTINGENCY EDP_AUTOTF1
  -570.9  27381     OPIC-115    115.00  27411     SONS-115    115.00 1   0.19005   -21.5  130.0 CONTINGENCY AHUA-NEJA_DOB
  -645.7  27131     ACAJ-115    115.00  27411     SONS-115    115.00 2  -0.12497    28.3  109.0 CONTINGENCY EDP-AHUA-1
  -682.0  27132     ACAJ2-115   115.00  27441     ATEO-115    115.00 1  -0.29513    58.7  260.0 CONTINGENCY AHUA-NEJA_DOB
  -697.3  28312     EDP2-230    230.00 3WNDTR EDP_TR230        WND 1 2  -0.29761    42.4  249.9 CONTINGENCY AHUA-NEJA_DOB
  -698.0  28161     AHUA-230    230.00  28311     EDP-230     230.00 2   0.36255   -42.5  295.6 CONTINGENCY ACAJ-ATEO
1....................................................................................................
 .           PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS(R)E     THU, MAR 12 2026  15:59     PAGE 3 .
 .                                                                                                  .
 .                   BASE DE DATOS DE EL SALVADOR                                                   .
 .                                                                                                  .
 .         *** TLTG IMPORT LIMIT OUTPUT FOR SUBSYSTEM ESAG2                            ***          .
 ....................................................................................................

 * MONITORED ELEMENTS OCCURRING     10 OR MORE TIMES

   NO. <--------------------- MONITORED ELEMENT --------------------->
 TIMES <--------- F R O M ---------> <----------- T O -----------> CKT
    39  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1  2

 Output completed