SISTEMA OPUESTO ACAJUTLA

###################################

 The working case has a largest mismatch of 0.0 MW at bus 14319 [THP-400     400.00]

 These subsystems were specified:
   # <------- SUBSYSTEM LABEL ------>  BUSES    # <------- SUBSYSTEM LABEL ------>  BUSES    # <------- SUBSYSTEM LABEL ------>  BUSES
   1 GUATEMALA                           483    2 ESAG1                                40    3 ESAG2                                26
   4 ACAJUTLA                             14    5 HONDURAS                            381    6 GUA-HON                             864

 Study system generation is         515.9 MW
 Opposing system generation is        0.1 MW
 Study system net interchange is    515.9 MW
1.......................................................................................................
 .             PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS(R)E     WED, MAR 13 2024  10:49      PAGE 1 .
 .                                                                                                     .
 .                    BASE DE DATOS DE EL SALVADOR- ESTUDIO DE RESTRICCIONES 2024                      .
 .                    DEMANDA MINIMA 2SEM 2025                                                         .
 .                                                                                                     .
 .          *** TLTG IMPORT LIMIT OUTPUT FOR BASE CASE                                    ***          .
 .......................................................................................................

 DISTRIBUTION FACTOR FILE:     G:\control\Estudios\ERT2024\simu\tltg\2025\ESA_Min2Sem25\dfx_ ESA_Min2Sem25.dfx
 SUBSYSTEM DESCRIPTION FILE:   G:\control\Estudios\ERT2024\simu\tltg\2025\subsistemas_TLTG.sub
 MONITORED ELEMENT FILE:       G:\control\Estudios\ERT2024\simu\tltg\2025\monitoreo_TLTG.mon
 CONTINGENCY DESCRIPTION FILE: G:\control\Estudios\ERT2024\simu\tltg\2025\ESA_TLTG_Cont.con

                                 PRE-SHIFT    DELTA  POST-SHIFT
 STUDY SYSTEM MW GENERATION:        515.9     -20.0     495.9
 OPPOSING SYSTEM MW GENERATION:       0.1      20.0      20.1
 STUDY SYSTEM NET INTERCHANGE:      515.9     -20.0     495.9

 <------------------ STUDY SYSTEM ------------------->  <----------------- OPPOSING SYSTEM ----------------->
                              <---- GENERATOR MW ---->                               <---- GENERATOR MW ---->
   BUS#-SCT X-- NAME --X BASKV    BASE   SHIFT  CHANGE    BUS#-SCT X-- NAME --X BASKV    BASE   SHIFT  CHANGE
  21081     3FEB-U1     13.800    30.7    29.6    -1.1   21136     M1-M3       13.800     0.1    20.1    20.0
  21082     3FEB-U2     13.800    30.7    29.6    -1.1
  21101     5NOV-U1     13.800    16.2    15.5    -0.6
  21102     5NOV-U2     13.800    16.2    15.5    -0.6
  21103     5NOV-U3     13.800    16.2    15.5    -0.6
  21104     5NOV-U4     13.800    14.3    13.7    -0.6
  21105     5NOV-U5     13.800    19.5    18.8    -0.7
  21106     5NOV-U6     13.800    37.3    36.0    -1.3
  21107     5NOV-U7     13.800    37.3    36.0    -1.3
  21111     GUAJ-U1     13.800    16.0    15.4    -0.6
  21171     CGRA-U1     13.800    54.5    51.7    -2.8
  21172     CGRA-U2     13.800    54.5    51.7    -2.8
  21181     15SE-U1     13.800    86.3    83.3    -2.9
  21182     15SE-U2     13.800    86.3    83.3    -2.9

 LOADINGS AT OR ABOVE 100.0 <------------- BASE CASE ------------->
 OF RATING ARE MARKED WITH '*'                                        INCR.          PRE-   POST-   LIMIT
                                                                      TRANS RATING  SHIFT   SHIFT    CASE    DISTR.
 <--------- F R O M --------->   <----------- T O ----------->  CKT   CAPAB    1      MW      MW      MW     FACTOR
  28371     NEJA-230    230.00   3WNDTR NEJA_TR_1        WND 1   1   -522.3   154    26.7    31.5   154.0* -0.24374
  28371     NEJA-230    230.00   3WNDTR NEJA_TR_2        WND 1   2   -522.3   154    26.7    31.5   154.0  -0.24374
  27131     ACAJ-115    115.00    27411     SONS-115    115.00   2   -706.9   109     5.4     8.3    81.9  -0.14657
  27381     OPIC-115    115.00    27411     SONS-115    115.00   1   -837.5   130     4.3     1.1   -79.4   0.16010
  27421     NCUS-115    115.00    27551     VOLC-115    115.00   1  -1040.0   260     5.5     0.4  -127.8   0.25529

  28312     EDP2-230    230.00   3WNDTR EDP_TR_2         WND 1   2  -1063.4   250    31.7    26.4  -106.7   0.26487
  28312     EDP2-230    230.00   3WNDTR EDP_TR_1         WND 1   1  -1075.7   250    31.3    26.0  -105.3   0.26146
  28161     AHUA-230    230.00    28311     EDP-230     230.00   2  -1127.3   265    31.5    26.2  -106.0   0.26317
  27421     NCUS-115    115.00    27461     STOM-115    115.00   1  -1205.1   259   -48.3   -43.2    85.1  -0.25529
  27161     AHUA-115    115.00    27351     SANA-115    115.00   1  -1206.7   129    11.5    13.4    62.2  -0.09714

  27132     ACAJ2-115   115.00    27441     ATEO-115    115.00   1  -1251.2   260    34.1    37.7   128.4  -0.18054
  27381     OPIC-115    115.00    27501     SMAT-115    115.00   1  -1261.6   260   -24.1   -19.6    93.5  -0.22514
  27371     NEJA-115    115.00    27501     SMAT-115    115.00   1  -1343.4   260    42.8    38.3   -74.7   0.22514
  27181     15SE-115    115.00    27431     SMAR-115    115.00   2  -1362.9   130    50.0    47.4   -19.0   0.13205
  27321     SRAF-115    115.00    27431     SMAR-115    115.00   1  -1402.7   260    94.4    89.3   -37.5   0.25239

  27431     SMAR-115    115.00    27461     STOM-115    115.00   1  -1430.3   260   105.3   100.2   -28.0   0.25529
  27371     NEJA-115    115.00    27561     APOP-115    115.00   1  -1472.2   260   -72.6   -68.1    45.3  -0.22571
  27171     CGRA-115    115.00    27371     NEJA-115    115.00   1  -1506.4   260    80.1    75.6   -37.8   0.22571
  27171     CGRA-115    115.00    27561     APOP-115    115.00   1  -1509.2   260    80.7    76.2   -37.1   0.22571
  27181     15SE-115    115.00    27321     SRAF-115    115.00   1  -1645.7   130    37.5    35.5   -15.6   0.10178

  27371     NEJA-115    115.00    27431     SMAR-115    115.00   1  -1771.2   260     0.1     3.0    76.7  -0.14676
  27081     3FEB-115    115.00    27181     15SE-115    115.00   1  -1781.7   128    59.6    57.5     4.7   0.10503
  27351     SANA-115    115.00    27381     OPIC-115    115.00   1  -1831.6   130    10.7    12.0    44.7  -0.06504
  27441     ATEO-115    115.00    27551     VOLC-115    115.00   1  -1833.9   260     3.4     6.2    76.5  -0.13989
  28161     AHUA-230    230.00    28371     NEJA-230    230.00   2  -1840.5   396   -18.0   -13.5    99.4  -0.22491

  27101     5NOV-115    115.00    27171     CGRA-115    115.00   1  -1937.4   260    79.8    76.3   -11.8   0.17540
  27301     SOYA-115    115.00    27371     NEJA-115    115.00   1  -2013.6   260   -29.4   -31.7   -89.2   0.11445
  27411     SONS-115    115.00    27441     ATEO-115    115.00   1  -2311.4   205    32.2    33.7    71.3  -0.07475
  27301     SOYA-115    115.00    27431     SMAR-115    115.00   1  -2507.3   260   -27.1   -24.8    32.7  -0.11445
  27161     AHUA-115    115.00    27411     SONS-115    115.00   1  -2788.3   130    33.0    31.8     2.6   0.05828

  27101     5NOV-115    115.00    27321     SRAF-115    115.00   1  -2915.8   260    77.1    74.8    16.7   0.11562
  27441     ATEO-115    115.00    27481     TALN-115    115.00   1  -3378.1   410    19.9    22.2    80.2  -0.11540
  27481     TALN-115    115.00    27551     VOLC-115    115.00   1  -3543.2   410     1.1     3.4    61.3  -0.11540
  27281     CHIN-115    115.00    27321     SRAF-115    115.00   1  -3652.4   130   -17.1   -17.7   -33.2   0.03091
  27281     CHIN-115    115.00    27391     TECO-115    115.00   1  -3652.9   130    17.1    17.7    33.2  -0.03091

  27391     TECO-115    115.00    27401     OZAT-115    115.00   1  -4131.9   130     2.3     2.9    18.4  -0.03091
  27341     SMIG-115    115.00    27401     OZAT-115    115.00   1  -4722.2   130    16.0    15.3    -0.2   0.03091
  27111     GUAJ-115    115.00    27351     SANA-115    115.00   1  -5282.9   129    40.1    39.4    23.3   0.03209
  27181     15SE-115    115.00    27211     BERL-115    115.00   1  -6484.0   129   -46.3   -46.6   -53.0   0.01271
  28161     AHUA-230    230.00   3WNDTR AHUA_TR_1        WND 1   1  -8491.7   154   -11.5   -11.1    -1.3  -0.01943

  28161     AHUA-230    230.00   3WNDTR AHUA_TR_2        WND 1   2  -8491.7   154   -11.5   -11.1    -1.3  -0.01943
  27181     15SE-115    115.00    27341     SMIG-115    115.00   1  -9239.4   130    38.2    37.8    28.7   0.01820
  27211     BERL-115    115.00    27341     SMIG-115    115.00   1  -14616.   130    55.8    55.5    49.1   0.01271
  28181     15SE-230    230.00    28371     NEJA-230    230.00   2  -18634.   396    44.7    45.1    54.6  -0.01883
  28181     15SE-230    230.00    29181     F-15SE-NNC  230.00   1  -23093.   521     2.5     2.1    -9.3   0.02267

  28161     AHUA-230    230.00    29162     F-AHU-MOY   230.00   1  -24257.   525     3.1     3.6    14.4  -0.02151
  28161     AHUA-230    230.00    29161     F-AHU-LVG   230.00   1  -24976.   396    -7.2    -6.9     1.2  -0.01614
  28181     15SE-230    230.00    29182     F-15SE-AGC  230.00   2  -26525.   396     1.7     1.4    -6.2   0.01499
  27171     CGRA-115    115.00    27321     SRAF-115    115.00   1  -36354.   130    18.1    18.1    16.0   0.00407
  27071     LANG-115    115.00    27371     NEJA-115    115.00   1  <-99999   130     0.0     0.0     0.0  -0.00000

  27111     GUAJ-115    115.00    27241     VENT-115    115.00   1  <-99999   130   -40.6   -40.6   -40.6  -0.00000
  27131     ACAJ-115    115.00    27132     ACAJ2-115   115.00   1  <-99999  NONE   -17.1   -23.0  -170.2   0.29313
  27131     ACAJ-115    115.00    27221     ALVA-115    115.00   1  <-99999    74     0.0     0.0     0.0   0.00000
  27132     ACAJ2-115   115.00    27133     TPTO-115    115.00   1  <-99999   110    -0.0    -0.0    -0.0  -0.00000
  27171     CGRA-115    115.00    27531     CHAL-115    115.00   1  <-99999   130     6.2     6.2     6.2   0.00000

  27201     ANTA-115    115.00    27471     PEDR-115    115.00   1  <-99999    75     0.0     0.0     0.0   0.00000
  27281     CHIN-115    115.00    27291     JIBO-115    115.00   1  <-99999   130     0.0     0.0     0.0   0.00000
  27341     SMIG-115    115.00    27511     HAVI-115    115.00   1  <-99999   260    25.2    25.2    25.2   0.00000
  27361     SANT-115    115.00    27551     VOLC-115    115.00   1  <-99999   260    11.6    11.6    11.6   0.00000
  27371     NEJA-115    115.00    27372     NEPO-115    115.00   1  <-99999  NONE     0.0     0.0     0.0   0.00000

  27401     OZAT-115    115.00    27402     CAPE115-FV  115.00   1  <-99999  NONE     0.0     0.0     0.0   0.00000
  27431     SMAR-115    115.00    27451     SBAR-115    115.00   2  <-99999   130    20.2    20.2    20.2   0.00000
  27461     STOM-115    115.00    27471     PEDR-115    115.00   1  <-99999   130    20.3    20.3    20.3   0.00000
  27481     TALN-115    115.00    27571     TAMA-115    115.00   1  <-99999   130     8.3     8.3     8.3   0.00000
  27491     LUNI-115    115.00    27511     HAVI-115    115.00   1  <-99999   260   -25.1   -25.1   -25.1  -0.00000

  27511     HAVI-115    115.00    27521     CHAP-115    115.00   1  <-99999   130     0.0     0.0     0.0   0.00000

 Contingency "INTR_GUAT_MOY" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "INTR_GUAT_LVG" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "INTR_HOND_NNC" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "INTR_HOND_AGC" has 1 bus(es) not connected back to a swing (type 3) bus
 Using a full dc network solution

 Contingency "SMIG-HAVI" has 5 bus(es) not connected back to a swing (type 3) bus

 Contingency "VOLC-SANT" has 4 bus(es) not connected back to a swing (type 3) bus
1.......................................................................................................................................................
 .                                     PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS(R)E     WED, MAR 13 2024  10:49                              PAGE 2 .
 .                                                                                                                                                     .
 .                                            BASE DE DATOS DE EL SALVADOR- ESTUDIO DE RESTRICCIONES 2024                                              .
 .                                            DEMANDA MINIMA 2SEM 2025                                                                                 .
 .                                                                                                                                                     .
 .                                   *** TLTG IMPORT LIMIT OUTPUT FOR SUBSYSTEM ESAG2                            ***                                   .
 .......................................................................................................................................................

 SOLUTION OF  53 SYSTEM CONDITIONS ATTEMPTED      0 INSOLUBLE SYSTEM CONDITIONS

   INCR.                                                                            PRE- RATING
   TRANS <--------------------- LIMITING ELEMENT --------------------->   DISTR.   SHIFT BAS/CNT
   CAPAB <--------- F R O M ---------> <----------- T O ----------->CKT   FACTOR     MW    1/1  <------------------ CONTINGENCY DESCRIPTION ------------------->
  -252.0  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.42606    46.6  154.0 CONTINGENCY NEJA_AUTOTF1
  -373.4  27131     ACAJ-115    115.00  27411     SONS-115    115.00 2  -0.33905   -17.6  109.0 CONTINGENCY ACAJ-AHUA_DOB
  -398.8  28371     NEJA-230    230.00 3WNDTR NEJA_TR_1        WND 1 1  -0.32357    24.9  154.0 CONTINGENCY VOLC-NCUS
  -398.8  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.32357    24.9  154.0 CONTINGENCY VOLC-NCUS
  -418.8  28371     NEJA-230    230.00 3WNDTR NEJA_TR_1        WND 1 1  -0.32462    18.0  154.0 CONTINGENCY SMAT-OPIC
  -418.8  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.32462    18.0  154.0 CONTINGENCY SMAT-OPIC
  -439.6  28371     NEJA-230    230.00 3WNDTR NEJA_TR_1        WND 1 1  -0.32462    11.3  154.0 CONTINGENCY NEJA-SMAT
  -439.6  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.32462    11.3  154.0 CONTINGENCY NEJA-SMAT
  -440.1  28371     NEJA-230    230.00 3WNDTR NEJA_TR_1        WND 1 1  -0.32357    11.6  154.0 CONTINGENCY NCUS-STOM
  -440.1  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.32357    11.6  154.0 CONTINGENCY NCUS-STOM
  -451.3  28371     NEJA-230    230.00 3WNDTR NEJA_TR_1        WND 1 1  -0.27078    31.8  154.0 CONTINGENCY ACAJ-ATEO
  -451.3  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.27078    31.8  154.0 CONTINGENCY ACAJ-ATEO
  -457.9  28371     NEJA-230    230.00 3WNDTR NEJA_TR_1        WND 1 1  -0.28011    25.7  154.0 CONTINGENCY OPIC-SONS
  -457.9  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.28011    25.7  154.0 CONTINGENCY OPIC-SONS
  -461.9  28371     NEJA-230    230.00 3WNDTR NEJA_TR_1        WND 1 1  -0.26911    29.7  154.0 CONTINGENCY AHUA-SANA
  -461.9  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.26911    29.7  154.0 CONTINGENCY AHUA-SANA
  -471.9  27131     ACAJ-115    115.00  27411     SONS-115    115.00 2  -0.21426     7.9  109.0 CONTINGENCY ACAJ-SONS
  -474.7  27131     ACAJ-115    115.00  27411     SONS-115    115.00 2  -0.19785    15.1  109.0 CONTINGENCY ACAJ-ATEO
  -477.5  28371     NEJA-230    230.00 3WNDTR NEJA_TR_1        WND 1 1  -0.26073    29.5  154.0 CONTINGENCY SANA-OPIC
  -477.5  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.26073    29.5  154.0 CONTINGENCY SANA-OPIC
  -495.2  28371     NEJA-230    230.00 3WNDTR NEJA_TR_1        WND 1 1  -0.32357    -6.3  154.0 CONTINGENCY SMAR-STOM
  -495.2* 28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1 2  -0.32357    -6.3  154.0 CONTINGENCY SMAR-STOM
  -496.3* 28371     NEJA-230    230.00 3WNDTR NEJA_TR_1        WND 1 1  -0.25056    29.6  154.0 CONTINGENCY SONS-ATEO
  -527.4  27381     OPIC-115    115.00  27411     SONS-115    115.00 1   0.27112    13.2  129.8 CONTINGENCY AHUA-NEJA_DOB
  -541.0  27381     OPIC-115    115.00  27411     SONS-115    115.00 1   0.27273    17.7  129.8 CONTINGENCY ACAJ-AHUA_DOB
  -549.8  27131     ACAJ-115    115.00  27411     SONS-115    115.00 2  -0.19557     1.5  109.0 CONTINGENCY AHUA-NEJA_DOB
  -583.6  27161     AHUA-115    115.00  27411     SONS-115    115.00 1   0.33517    66.1  129.5 CONTINGENCY ACAJ-AHUA_DOB
  -591.6  27381     OPIC-115    115.00  27411     SONS-115    115.00 1   0.22914     5.8  129.8 CONTINGENCY VOLC-NCUS
  -622.2  27161     AHUA-115    115.00  27351     SANA-115    115.00 1  -0.20189     3.1  128.7 CONTINGENCY AHUA-NEJA_DOB
  -627.3  27131     ACAJ-115    115.00  27411     SONS-115    115.00 2  -0.16955     2.7  109.0 CONTINGENCY EDP-AHUA-1
  -635.0  27131     ACAJ-115    115.00  27411     SONS-115    115.00 2  -0.16701     3.0  109.0 CONTINGENCY ACAJ_AUTOTF1
  -642.1  27381     OPIC-115    115.00  27411     SONS-115    115.00 1   0.22914    17.3  129.8 CONTINGENCY NCUS-STOM
  -651.0  28312     EDP2-230    230.00 3WNDTR EDP_TR_2         WND 1 2   0.47043    56.2  250.0 CONTINGENCY ACAJ_AUTOTF1
  -662.5  27131     ACAJ-115    115.00  27411     SONS-115    115.00 2  -0.15499     6.3  109.0 CONTINGENCY NEJA_AUTOTF1
  -663.2  27131     ACAJ-115    115.00  27411     SONS-115    115.00 2  -0.15754     4.5  109.0 CONTINGENCY AHUA-NEJA-1
  -666.0  27381     OPIC-115    115.00  27411     SONS-115    115.00 1   0.19510     0.1  129.8 CONTINGENCY AHUA-SANA
  -678.8  27131     ACAJ-115    115.00  27411     SONS-115    115.00 2  -0.15172     6.0  109.0 CONTINGENCY AHUA-SANA
  -680.6* 27131     ACAJ-115    115.00  27411     SONS-115    115.00 2  -0.14782     8.4  109.0 CONTINGENCY NEJA-15SE_DOB
  -683.4  27381     OPIC-115    115.00  27501     SMAT-115    115.00 1  -0.44092   -41.4  259.9 CONTINGENCY AHUA-NEJA_DOB
  -691.7  28161     AHUA-230    230.00  28311     EDP-230     230.00 2   0.46349    55.4  265.2 CONTINGENCY EDP-AHUA-1
  -698.2  27421     NCUS-115    115.00  27551     VOLC-115    115.00 1   0.39645    16.8  260.0 CONTINGENCY AHUA-NEJA_DOB
1....................................................................................................
 .           PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS(R)E     WED, MAR 13 2024  10:49     PAGE 3 .
 .                                                                                                  .
 .                   BASE DE DATOS DE EL SALVADOR- ESTUDIO DE RESTRICCIONES 2024                    .
 .                   DEMANDA MINIMA 2SEM 2025                                                       .
 .                                                                                                  .
 .         *** TLTG IMPORT LIMIT OUTPUT FOR SUBSYSTEM ESAG2                            ***          .
 ....................................................................................................

 * MONITORED ELEMENTS OCCURRING     10 OR MORE TIMES

   NO. <--------------------- MONITORED ELEMENT --------------------->
 TIMES <--------- F R O M ---------> <----------- T O -----------> CKT
    29  28371     NEJA-230    230.00 3WNDTR NEJA_TR_2        WND 1  2
    28  28371     NEJA-230    230.00 3WNDTR NEJA_TR_1        WND 1  1
    10  27131     ACAJ-115    115.00  27411     SONS-115    115.00  2

 Output completed